Contractor checking a bowed concrete-block foundation wall against a freely hanging plumb line

Does a Bowed Block Wall Qualify for Straps?

A bowed concrete-block foundation wall may qualify for Nolan Basement Wall Straps when existing inward deflection does not exceed 2 inches and the wall, backfill, soil, masonry, spacing, and fastening conditions fit the sealed design report and instructions. The system is designed to resist additional inward movement; it does not straighten the existing bow.

TL;DR
  • The wall must be qualifying CMU/block construction.
  • Existing inward deflection must not exceed 2 inches.
  • Wall height, backfill height, and soil class determine maximum spacing.
  • The masonry must be sound enough to receive every required fastener.
  • Basement Wall Straps are designed to resist additional inward movement; they do not straighten the wall or remove cracks.

What is the first qualification test?

Confirm the wall type. Nolan’s instructions apply to concrete masonry unit (CMU/block) foundation walls within the sealed design report.

Do not transfer the report’s limits or spacing table to:

  • Poured-concrete walls.
  • Stone foundations.
  • Brick foundations.
  • Wood-framed foundation walls.
  • Freestanding retaining walls.

Those conditions need separate documentation.

How much existing inward deflection is allowed?

Nolan states that the straps are not recommended where existing inward wall deflection exceeds 2 inches. The current instructions say to stop and obtain an engineer evaluation above that limit.

That is the published maximum existing inward deflection for this product application. It is not a universal rule for deciding whether a wall needs replacement, and it does not mean every wall below 2 inches automatically qualifies.

What other conditions must qualify?

A wall within the 2-inch limit must also satisfy the approved design and installation conditions.

Verify:

  • Wall height.
  • Maximum exterior backfill height.
  • Soil class.
  • Masonry condition.
  • Wall-face access.
  • Required strap spacing.
  • Top-course condition.
  • Ability to install every specified fastener.

Stop if the masonry is loose, severely cracked, deteriorated, displaced, crushed, or unable to receive the required fastening.

Does the system straighten the wall?

No. Nolan’s product information describes a system designed to resist additional inward movement. It does not remove an existing crack or bow.

Do not promise that installation will:

  • Return the wall to plumb.
  • Close horizontal mortar-joint cracks.
  • Pull displaced block back into position.
  • Correct footing movement.
  • Eliminate water entry.
  • Restore an unknown original capacity.

The product’s documented benefit is stabilization against additional inward movement within the approved design.

How is maximum spacing selected?

Use Nolan’s separate table by matching wall height, maximum backfill height, and soil class.

For example, an 8-foot wall with 8 feet of backfill has maximum spacing of:

  • 24 inches in Class I soil.
  • 16 inches in Class II soil.
  • 8 inches in Class III soil.

The verified soil class determines which value applies to that wall and backfill combination.  If soil class is unknown, use Class III which is the most conservative or you may contact a geotechnical engineer to have soils tested. 

The current instructions state that spacing is project-specific.

What does the report’s test prove—and not prove?

Nolan’s report describes testing on a nominal 8-inch concrete-block wall that was 11 courses, or about 7 feet 4 inches, tall. The test simulated a triangular 60 psf lateral-earth-pressure distribution. The wall deflected 5/8 inch near its center at about one-quarter of the maximum design load and did not deflect significantly further at full load.

That result belongs to the stated test assembly and loading. It does not create a general 5/8-inch installation limit, prove performance for every block wall, or replace the separate 2-inch existing-deflection limit.

The 5,500-pound value is the strap’s published breaking strength, not its allowable design load or the capacity of an installed wall system. The calculated 2,078-pound tension applies to the report’s stated governing design case.

When should work stop?

Do not proceed from this article alone when:

  • Existing inward deflection exceeds 2 inches.
  • Wall type is not CMU/block.
  • Masonry is loose, severely cracked, deteriorated, or displaced.
  • Wall height, backfill height, or soil class is unknown.
  • The wall falls outside the sealed report.
  • Required spacing cannot be achieved.
  • Every required fastener cannot be installed.
  • The wall or supporting structure has another condition needing evaluation.

Contact Nolan or the project engineer rather than selecting a different spacing or field modification.

Which documents should be used?

Use:

Use the current installation instructions together with the design report and spacing table.

FAQ

What wall type qualifies for Nolan Basement Wall Straps?

The supplied report and current instructions cover qualifying concrete masonry unit, or CMU/block, foundation walls.

What is the maximum existing inward deflection?

Nolan sets a 2-inch maximum. Stop and obtain an engineer evaluation when deflection exceeds it.

Does a wall under 2 inches automatically qualify?

No. Wall height, backfill, soil class, masonry condition, spacing, fastening, and the sealed report must also be checked.

Will the straps straighten a bowed wall?

No. The system is designed to resist additional inward movement; it does not remove the existing bow or crack.

How far apart are the straps installed?

Maximum spacing is project-specific and comes from Nolan’s table using wall height, backfill height, and soil class.

What if the masonry is severely cracked or cannot receive all fasteners?

Stop work and contact the engineer; the current instructions do not allow the installation to be improvised.

One last thing

Qualification is not based on bow measurement alone. Confirm CMU construction, the 2-inch limit, all three spacing-table inputs, sound fastening conditions, and the applicable sealed report before selecting the system.

 

Back to blog